Florida requirements guide
Florida fire extinguisher tag requirements and licensing, from rule 69A-21
Last updated

In Florida, portable extinguisher service is regulated by the State Fire Marshal under chapter 633 of the Florida Statutes and Florida Administrative Code chapter 69A-21, "Fire Extinguishers and Pre-engineered Systems." Florida spells out the tag contents, the tag size, who may fill it out, and what the matching invoice must show. This page walks through those rules and quotes the text so you can check it yourself. The 69A-21 rules quoted here were last amended in 2001, except 69A-21.237, last amended in 1993, and the NFPA adoption rule 69A-3.012 took effect December 31, 2023; confirm the current text on flrules.org before relying on it.
When a tag is required, and who may attach it
Rule 69A-21.240 sets the basic obligation: "Each portable extinguisher which has been subjected to any type of service shall have an approved standard record tag securely attached thereto, before being placed into service."
The same rule ties the tag to a specific person. The tag "shall indicate that the person, whose name and permit number appear on the tag, has serviced the fire extinguisher in compliance with these rules and the standards adopted herein," and "Only the person performing the service shall prepare and affix the appropriate service tag." A tag also may not go on an extinguisher that does not comply until the violation is corrected.
In practice this means the tech who did the work fills out the tag. A tag pre-filled at the shop with another tech's name or permit number does not meet the rule's wording.
What the service tag must show
Rule 69A-21.241(1)(b) lists seven items that every standard service tag, pressure sensitive label or decal must carry:
- "Do Not Remove."
- Serial number of the extinguisher.
- Name of the person who performed the service. The rule adds: "Initials are not acceptable."
- Permit number of the person who serviced the extinguisher.
- The type of service performed.
- The type of extinguisher involved.
- The month and year of service, shown "by means of perforation so that only the specific month is indicated."
Paragraph (1)(f) adds a company block: "The name, street address and telephone number of the company or organization performing said service must be printed on the front center section" of the tag, label or decal. Paragraph (1)(g) says the rest of the tag "shall contain no erroneous, false, or misleading statements."
Tag size, format and color
| Item | What the rule says | Paragraph |
|---|---|---|
| Format | Tie-on tag, or a pressure sensitive label or decal meeting the same specifications, arranged as shown in the rule's Figure A | (1)(a) |
| Size | No less than 2 1/2 inches and no greater than 3 inches, by no less than 5 1/4 inches and no greater than 5 3/4 inches | (1)(d) |
| Printing color | "the printing may be any color" | (1)(c) |
| Years printed | Any number of years, not more than five | (1)(a) |
| New tag | A new tag, label or decal each time a service is performed | (1)(e) |
The rule text sets no color for the tag itself; it only addresses the printing color, and leaves that open. The layout is set by Figure A in the rule, which is an image in the official document; check it on flrules.org when you order tags from a printer.
Out-of-date tags come off first. Rule 69A-21.237(3): "All tags, labels and decals required by the State Fire Marshal which are out of date shall be removed before a current tag or label is placed on the extinguisher."
Verification collar, 6 year record tag and hydro tag
Annual service is only one of the markings Florida regulates. Three more apply when a unit is opened or tested:
- Verification of service collar, 69A-21.241(2): a collar meeting NFPA 10 (the rule text cites Section 4-4.4.2, an older edition's numbering) is required "each time an extinguisher is opened for any type of service or for any purpose." A new collar is required each time, and "No advertisement or any other information shall be included on the verification service collar."
- 6 year maintenance record tag for certain stored pressure extinguishers, 69A-21.237(2)(b): a decal affixed "by a heatless process" on the shell, metallized or equally durable, that is "self-destructive when removal from an extinguisher shell is attempted." It shows the year and month of the 6 year maintenance and "the name of the agency performing the maintenance."
- Hydrostatic test record tag, 69A-21.245: must comply with NFPA 10 and the referenced federal cylinder rules, and "shall remain legible for the duration of the performed hydrotest interval."
Rule 69A-21.237(2), which is headed "Six Year Maintenance for Certain Stored Pressure Extinguishers," also says in paragraph (a) that the 6 year interval runs from the date of manufacture, then from the date of recharge or internal maintenance, and that complete 6 year maintenance "shall be performed when any extinguisher subject to this rule is opened for any purpose."
The invoice has to match the tag
Rule 69A-21.251 is easy to overlook and is where paper systems tend to slip. Invoices must show the dealer's business name, physical business address and license number, and "The license number on the invoice shall coincide with the permit number on the tags which are attached to the extinguishers being invoiced for service."
Invoices must also list the serial number of each extinguisher and identify, per serial number, the services performed and any parts replaced. That detail may be on a separate sheet attached to the invoice. If your invoice only says "annual service, 14 units," it does not meet this rule.
Who may service: license and permit classes
Section 633.304, Florida Statutes, requires two credentials. The business needs a fire equipment dealer license, and "Each individual actually performing the work" needs a permit. A permittee is limited to work "no more extensive than the class of license held by the licensee under whom the permittee is working."
| Class | Scope in the statute |
|---|---|
| Class A | Service, recharge, repair, install or inspect all types of fire extinguishers, and hydrostatic tests on all types |
| Class B | Same as A, including recharging carbon dioxide units, with hydrostatic tests on all types except carbon dioxide units |
| Class C | Same as A, except recharging carbon dioxide units, with hydrostatic tests on all types except carbon dioxide units |
| Class D | Service, repair, recharge, hydrotest, install or inspect all types of preengineered fire extinguishing systems |
Permits come in two kinds under s. 633.304(3): a portable permit for portable extinguishers and a preengineered permit for preengineered systems. Rule 69A-21.103 adds that a permit is valid only for work for the licensee it was issued under, a tech who changes employers needs a new permit, and the licensee must notify the Regulatory Licensing Section in writing within fifteen days when a permittee leaves.
- Renewal: licenses and permits expire on December 31 of each odd-numbered year (s. 633.304(4)(a)).
- Continuing education: at least 16 hours per renewal period for licensees and permittees, and the licensee must make sure its permittees meet theirs (s. 633.304(4)(b)).
- Carry it: a permittee must have the permit and a photo identification card on their person while working (s. 633.304(7)).
- Trainees: a trainee may not do permit work unless a currently permitted individual is physically present, and "No more than two trainees shall be under the supervision of a single trainer" (s. 633.304(5)).
- Insurance minimums: $300,000 for Class A or D, $200,000 for Class B, $100,000 for Class C (s. 633.304(4)(d)3, with the same amounts set in rule 69A-21.112).
Pre-engineered systems use the same tag
If your shop also services pre-engineered systems, rule 69A-21.303 points back to the same specifications: the standard service tag "shall comply with the specifications embodied in subsection 69A-21.241(1)," is completed and affixed as described in 69A-21.240, and the collar, 6 year record tag and hydro tag rules also apply.
How Florida adopts NFPA 10
Rule 69A-21.203 requires licensed dealers to "install, inspect, maintain, or recharge portable fire extinguishers in accordance with NFPA 10," using "the edition as adopted in rule chapter 69A-3," and says its provisions "are mandatory." The rule does not name a year itself.
The year comes from rule 69A-3.012, which adopts the Florida Fire Prevention Code, 8th Edition (2023), and lists "NFPA 10, 2018 edition, Standard for Portable Fire Extinguishers." The same list adopts NFPA 17A (2021 edition) for wet chemical systems and NFPA 96 (2021 edition) for commercial cooking operations. 69A-3.012 was last amended effective 12-31-23. The flrules.org history for the rule shows a 2026 triennial update in progress (a notice of proposed rule published June 12, 2026), so these editions may change; check the rule page for the current status.
Some 69A-21 rules still cite NFPA 10 section numbers in an older edition's format (for example 4-4.4.2 for the collar and 4-4.2 for the weighing exception). Do not look for those numbers in the 2018 edition; look up the topic in the edition Florida currently adopts.
Sources
- FAC chapter 69A-21, Fire Extinguishers and Pre-engineered Systems (flrules.org)
- FAC 69A-21.240, Standard Service Tags, Requirements
- FAC 69A-21.241, Standard Service Tags, Specifications
- FAC 69A-21.237, Inspection, Maintenance and Hydrostatic Tests; Recharge, Repair, Replacement
- FAC 69A-21.245, Hydrostatic Tests; Record Tag
- FAC 69A-21.251, Invoices
- FAC 69A-21.103, Permit
- FAC 69A-21.112, Insurance Requirements
- FAC 69A-21.203, Standards of National Fire Protection Association Adopted
- FAC 69A-21.303, Standard Service Tag (pre-engineered systems)
- FAC 69A-3.012, Standards of the National Fire Protection Association and Other Standards Adopted
- Florida Statutes s. 633.304, Fire suppression equipment; license to install or maintain (2026)
- FAC 69A-3.012 rule history and notices (flrules.org)